Page - 64/73 AESZP0BA – AC1 SSL SENSORED - FREE VERSION - User Manual
- A Power failure or a Logic Failure occured in the controller.
In this case it is necessary to substituite the controller.
2) VMN HIGH
MDI-PRC Code = 31
- Cause: Before to switch the main contactor on, the SW turns on
sequencely the Bottom side Power Mosfets and expects the
phase V voltage falls to GND value. If the phase V remains
high level this alarm occurs.
- Remedy: Two possibilities:
- At least a motor phase is not connected to the controller
or broken.
- A Power Failure (e.g. a Bottom side Power Mosfet
opened) or a Logic Failure occured in the controller.
In this case it is necessary to substituite the controller
3) VMN LOW
MDI-PRC Code = 30
- Cause: Before to switch the main contactor on, the SW turns on
sequencely the Top side Power Mosfets and expects the phase
V voltage increases toward the rail capacitor value. If the phase
V does not increases this alarm occurs.
This alarm may occur also when the initial diagnosis is
overcome, and so the Main Contactor is expected to be
closed.Then, when the operator asks the truck moving but the
+Batt terminal of the controller is lower voltage than the Battery
voltage, this alarm occurs (Main Contactor has lost the
contactation although it is closed).
- Remedy: If the problem occurs before the Main Contactor closes,
probably a Power failure (e.g. a Bottom side Power Mosfet
short circuited or a Top side Power Mosfet broken) or a Logic
Failure occured in the controller. If the problem occurs when the
operator turns the truck moving the problem is the Battery
positive is not connected to the +Batt terminal of the controller
(check the continuity of the main contactor).
If the problem occurs permanently it is necessary to substituite
the controller.
14.1.4 Four Blinks Alarms
1) VACC NOT OK
MDI-PRC Code = 78
- Cause: The test is made at key-on and after 20sec that both the travel
demands have turned disactive. This alarm occurs if the
ACCELERATOR reading in the TESTER menu’ is higher than
1.0V (it means the wiper of the potentiometer is higher than
2Vdc) when the accelerator is released.
- Remedy: Check the mechanical calibration and the functionality of the
potentiometer.
2) PEDAL WIRE KO
MDI-PRC Code = 86
- Cause: The SW continuously checks for the connection of the two
supply ends of the potentiometer in the accelerator. The test
consists of reading the voltage drop on a sense diode,
connected between NPOT (CNB#11) and GND and cascaded
Vista de página 63