Page - 46/73 AESZP0BA – AC1 SSL SENSORED - FREE VERSION - User Manual
15) INCHING SPEED
(Standard version only because the inching switches are used for the Lifting
and Lowering switches in the MDI-PRC version). Hz value. It determines the
speed when the "Inching function" is active (see 12.4.1.3-4 SET INPUT#2,
SET INPUT#3).
16) INCHING TIME
(Standard version only because the inching switches are used for the Lifting
and Lowering switches in the MDI-PRC version). Level 0 to 9. It determines
the during time when the "Inching function" is active.
17) AUXILIARY TIME
Time units value (seconds). For the encoder version, it determines the time
duration the truck is kept on the ramp if the STOP ON RAMP option is ON.
18) MIN VALVE 1
(MDI-PRC version only). 0 to 255 digit. This parameter determines the
minimum voltage applied on the EVP1 when the position of the potentiometer
on CNA#18 is at the minimum. This parameter is not effective if the EVP1 is
programmed like a On/Off valve (see 12.4.1.16 – VALVE 1 TYPE). The
EVP1 is connected on the pin 8 of the MDI-PRC (see TRUCK TYPE –
12.4.1.18 – for the handling).
19) MIN VALVE 2
(MDI-PRC version only). 0 to 255 digit. This parameter determines the
minimum voltage applied on the EVP2 when the position of the potentiometer
on CNA#18 is at the minimum. This parameter is not effective if the EVP2 is
programmed like a On/Off valve (see 12.4.1.17 – VALVE 2 TYPE). The
EVP2 is connected on the pin 9 of the MDI-PRC (see TRUCK TYPE –
12.4.1.18 – for the handling).
20) MAX VALVE 1
(MDI-PRC version only). 0 to 255 digit. This parameter determines the
maximum voltage applied on the EVP1 when the position of the
potentiometer on CNA#18 is at the maximum. If the EVP1 is programmed
like a On/Off valve (see 12.4.1.16 – VALVE 1 TYPE), this parameter
determines the fixed voltage applied on the electrovalve coil . The EVP1 is
connected on the pin 8 of the MDI-PRC (see TRUCK TYPE – 12.4.1.18 – for
the handling).
21) MAX VALVE 2
(MDI-PRC version only). 0 to 255 digit. This parameter determines the
maximum voltage applied on the EVP2 when the position of the
potentiometer on CNA#18 is at the maximum. If the EVP2 is programmed
like a On/Off valve (see 12.4.1.17 – VALVE 2 TYPE), this parameter
determines the fixed voltage applied on the electrovalve coil. The EVP2 is
connected on the pin 9 of the MDI-PRC (see TRUCK TYPE – 12.4.1.18 – for
the handling).
22) VALVES VOLTAGE
(MDI-PRC version only). A nominal Battery voltage from 12V to 120V. This
parameter specifies the nominal voltage of the On/Off valves coil (EVD1 and
EVD2 connected to pin #6 and pin#4 of the MDI-PRC). The MDI-PRC,
supported by the AC1, is able to control Electrovalves at a nominal voltage
lower than the Battery voltage. For example Battery to 48V and Valves to